Operating Limits

Operating Limits

Cooling

Heating

(°F)

(°C)

(°F)

(°C)

Air Limits

Min. Ambient Air

45

7.2

45

7.2

Rated Ambient Air

80

26.7

70

21.1

Max. Ambient Air

100

37.8

85

29.4

Min. Entering Air

50

10.0

40

4.4

Rated Entering Air db/wb

80.6/66.2

27/19

68

20.0

Max. Entering Air db/wb

110/83

43/28.3

80

26.7

Water Limits

Min. Entering Water

30

-1.1

20

-6.7

Normal Entering Water

50-110

10-43.3

30-70

-1.1

Max. Entering Water

120

48.9

90

32.2

NOTE: Minimum/maximum limits are only for start-up conditions, and
are meant for bringing the space up to occupancy temperature. Units
are not designed to operate at the minimum/maximum conditions on
a regular basis. The operating limits are dependant upon three primary
factors: 1) water temperature, 2) return air temperature, and 3) ambient
temperature. When any of the factors are at the minimum or maximum
levels, the other two factors must be at the normal level for proper and
reliable unit operation.

Operating Parameters

Single Speed Models

Entering Water

Temp °F

Water Flow

gpm/ton

Cooling -- No Hot Water Generation

Suction Pressure

psig

Discharge Pres-

sure psig

Superheat

Subcooling

Water Temp Rise

°F

Air Temp Drop

°F DB

30

1.5

115 - 125

150 - 170

20 - 35

10 - 17

17 - 22

17 - 23

3.0

105 - 120

130 - 145

20 - 35

10 - 17

8 - 10

17 - 23

50

1.5

130 - 140

215 - 235

12 - 20

8 - 14

16 - 22

17 - 23

3.0

128 - 138

190 - 210

12 - 20

8 - 14

8 - 12

17 - 23

70

1.5

138 - 148

280 - 310

10 - 16

10 - 16

15 - 21

17 - 23

3.0

136 - 146

250 - 280

10 - 16

8 - 14

7 - 13

17 - 23

90

1.5

145 - 155

350 - 380

9 - 14

10 - 16

14 - 20

17 - 23

3.0

143 - 153

320 - 350

9 - 14

8 - 14

6 - 10

17 - 23

110

1.5

145 - 155

420 - 450

9 - 14

10 - 16

14 - 20

17 - 23

3.0

143 - 153

405 - 435

9 - 14

8 - 14

6 - 10

17 - 23

Entering Water

Temp °F

Water Flow

gpm/ton

Heating - No Hot Water Generation

Suction Pressure

psig

Discharge Pres-

sure psig

Superheat

Subcooling

Water Temp Drop

°F

Air Temp Rise

°F DB

30

1.5

73 - 85

270 - 305

8 - 14

3 - 10

6 - 10

15 - 21

3.0

77 - 90

280 - 315

8 - 14

3 - 10

4 - 8

17 - 23

50

1.5

97 - 110

290 - 325

10 - 16

3 - 10

9 - 13

22 - 28

3.0

102 - 115

300 - 335

10 - 16

3 - 10

7 - 11

24 - 30

70

1.5

130 - 145

320 - 355

13 - 19

3 - 10

10 - 14

30 - 36

3.0

135 - 150

325 - 360

13 - 19

3 - 10

8 - 12

32 - 38

90

1.5

150 - 160

350 - 390

13 - 19

3 - 10

10 - 14

30 - 36

3.0

155 - 165

365 - 405

13 - 19

3 - 10

8 - 12

32 - 38

110

1.5

3.0

NOTE: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.

Heating performance based on entering air temperature of 70º F DB.

2/15/12

Advertising