Setting the signal runtime, Calibration – Pilz PSS SB TESTER D User Manual

Page 15

Advertising
background image

Operating Manual: PSS SB TESTER

4-5

Setting the signal runtime

To measure the length of the bus cable you will need to enter the signal
runtime. The ex-works setting for the signal runtime is 4.5 ns/m. This value
is valid for the Pilz standard cable for SafetyBUS p (order no. 311 070). If
you use a cable with a different signal runtime, you will need to amend the
set value.

• Press F2 in the “Start” window.

• The “Settings” window opens. Use the arrow keys to move the cursor to

the symbol for “Signal runtime”

and press VAL.

• Use the arrow keys to enter the password “7041” and press VAL.

• The signal runtime is displayed. Use the arrow keys to set the signal

runtime to the required value.

• Press VAL to save the setting.

The current setting is saved. A message confirms that the setting has been
saved. The “Settings” window is then displayed again. You can return to
the “Start” window by pressing ESC.

The setting is stored in a memory that is supplied by the battery. If the
battery is removed, the contents of the memory will be retained for 10
minutes. If it takes longer for the battery to be replaced, the contents of the
memory will be lost.

Calibration

Calibration is reserved for Pilz customer service.

Advertising
This manual is related to the following products: