Separate tests: testing the signal edges, Tests/measurements – Pilz PSS SB TESTER D User Manual

Page 38

Advertising
background image

Tests/Measurements

5-20

Operating Manual: PSS SB TESTER

Example for “Dom. Level CAN_H”:

lower limit: 2.8 V
upper limit: 4.5 V
measured value: 3.5 V
test result: OK

Separate tests: Testing the signal edges

Abbreviations for these separate tests in the “Device xx” window:

• Rising edge CAN_H

• Falling edge CAN_H

• Rising edge CAN_L

• Falling edge CAN_L

Each device on SafetyBUS p is tested to ensure the signals it is sending
have the correct edges. The rise and fall time of the signals on CAN_H and
CAN_L are measured.

The measured time is shown in the detailed display of the result from
these separate tests.

Example for “Rising edge CAN_H”:

measured value: 86 ns

Fig. 5-11: Rise/fall time

Mean signal - 10 %

Mean signal +10 %

Rise time

Fall time

Advertising