Performing the length measurement – Pilz PSS SB TESTER D User Manual

Page 31

Advertising
background image

Operating Manual: PSS SB TESTER

5-13

Performing the length measurement

• Add the PSS SB TESTER to SafetyBUS p as shown in Figs. 5-3 to 5-6.

• Switch on the PSS SB TESTER.

• Highlight the

symbol in the “Start” window and press VAL.

• The “SafetyBUS p” window opens, in which you can select the test/

measurement. Use the arrow keys to move the cursor to the symbol for

“Length measurement”

and press VAL.

• The following question is displayed: “SafetyBUS p is switched off?”.

Make sure that SafetyBUS p is switched off, i.e. all devices on
SafetyBUS p must be switched off.
On the PSS SB BRIDGE, both sides of the Bridge must be without
voltage.

• Press VAL.

When the test is complete, a measured curve appears on the display.
Fig. 5-7 shows a typical measured curve.

Fig. 5-7: Typical measured curve for length measurement