----- Relay Station CBS-8 -------- --- Page No. 27
Number of reclosures.
)
Value between 0 and 10 reclosures.
If, after these attempts, reclosure has not been successful, the relay in
question remains blocked and has to be manually or remotely reset to unblock it.
Note:
Æ
If the preset number of reclosures is 0, they remain deactivated.
Æ
Reclosures are returned to zero when double the time between
reclosures has elapsed.