CIRCUTOR CBS8 (Available until stocks) User Manual

Page 8

Advertising
background image

----- Relay Station CBS-8 -------- --- Page No. 7

b.- Maximum admissible current: According to the transformer used.

WGxx 30 mA - 3 A

WGPxx 300 mA - 30 A

c.- Operating conditions:

-

Operating temperature

:

-10 ºC to +50 ºC

-

Relative humidity

:

5 to 95 % HR (without condensation)

-

Altitude :

up to 2000 m

d.- Safety:

-

Designed for category III installations - 300 V AC (EN 61010).

-

Electric shock protection by class II double isolation.

Installation:

The equipment is to be installed on 46277 DIN rail (EN 50022). All connections

are to be inside the electrical casing.

Remember that the terminals can be dangerous if touched when the equipment is
connected. Removing covers or parts may give access to parts that are dangerous if
touched. The equipment must not be used until it is completely installed.

The equipment must be connected to the power supply circuit with a minimum

1 mm

2

cable and protected with gl (IEC 269) or M type fuse between 0.5 and 2 A. It

must be fitted with a short circuit breaking element or equivalent to disconnect it from
the power supply.

Advertising