Tempest Thunder User Manual

Page 30

Advertising
background image

Thunder Enclosure User Manual

page

30

DEC3.3 Control Parameters

Temperature and Humidity Ranges:

Notes:

1 In moving light enclosures the temperature sensor is located in the exhaust

airflow. Temperatures shown may be higher than those around the luminaire.

2 We recommend using the factory default settings for several weeks or months

before making any changes. In most cases they will not be necessary.

Max Humidity Range 50-90%, Default 80%

The threshold at which air inside the enclosure is heated to raise dewpoint and

prevent condensation. Setting a higher Max Humidity is not a bad thing in high-

humidity climates. Setting the Max Humidity too low will result in unnecessary

heating and excessive energy use. So set the Max Humidity at the top end of the

relative humidity likely to be experienced on site.

DMX Address Range 001-510, Default 001

Sets the DMX address for the lamp relay control. (See also DMX Response)

Set Temp Units Display Degrees Celsius or Fahrenheit. Default Celsius

Note that temperature settings must always be Celsius.

Lamp Hours

Default 0000

Counts lamp hours – you must reset to zero when changing lamps.

Lamp On Point The lamp current at which DEC detects the luminaire/luminaire lamp is running.

Default is 1 Amp, which allows for equipment fans and power supplies to run

without changing the air in the enclosure. Lamp on point may be set in 0.2 Amp

increments between 0.2 Amps and 2.0 Amps.

Start-up Validation

Trip Temp
(55-70˚C, Default 60 ˚C)

Upper Temp
(35-50˚C, Default 40 ˚C)

Trend Temp
(Dynamic)

IdealTemp (Dynamic, based
on Relative Humidity)

LowerTemp
(0-10˚C, Default 0 ˚C)

Cooling Fan(s)

Heater(s)

Relative Humidity

(50-90%,

Default 80%)

Low

High

Advertising
This manual is related to the following products: