Hurricane Enclosure User Manual

page 46

Control Interface Operation

The Control Interface is normally LOCKED.

To UNLOCK, touch

ESC and OK together for 5 seconds.

You are now in the

CONTROL MENU

Use the arrow keys to scroll up and down the menu.

Use

OK, to enter a menu item, then the arrow keys to set

the item parameter, or to scroll to the next menu level.

Use

ESC to back up a level, and OK to confirm settings.


CONTROL MENU
DMX SET
(if DMX/RDM mode 2 or 3 is selected)

Select a DMX starting address in the range 001 to 510

1 – Lamp Relay

In RDM Mode 3 an addition two slots are required

2 – Fan Relay

3 – Heater Relay

Note that the DMX control is designed using a SAFETY pile-on Logic. In other words, the

DMX input can only override automatic settings in a safe manner. For example, if the

enclosure has switched off the lamp relay due to an over-temperature condition, the DMX

input cannot switch it on, if the fans are running because of Overtemp, the DMX input

cannot turn them off, and so on.

The DMX SET menu can be ignored if the DEC3 is in Standalone or DMX/RDM Mode 1 (RDM

Monitor) mode.
SET LAMP HOURS TO 0

The lamp hour counter needs to be reset each time you change the lamp in the

fixture/projector. Make this a part of your maintenance instructions.

STATUS DISPLAY

View Temperature (in Celsius) and Relative Humidity (in %) inside the enclosure. Note that

in Tornado moving light enclosures the temp/humidity sensor is located in the exhaust

airflow, which may be significantly warmer than ambient.

HUMIDITY SET

The humidity level above which the heater kicks in to remove humidity from incoming air

(default 80%, permissible range 50-90%). This setting should not normally be changed.

TEMP SET

Set three temperature trigger points for Top, Cutoff and Bottom temperatures.
TOP TEMP
The desired upper temperature limit for normal operation

(default 40°C, permissible range 35-45°C).

When the DEC3 sees air above this temperature, but below the additional Cutoff

temperature (see below), it indicates a temperature error. This is not dangerous, but may

reduce lamp life.
CUTOFF TEMP

Lamp

Heater

Fan

Relay

On

DMX

Temp

ESC

OK

Depending on the Operating Mode

selected, and present status, DEC3’s

display shows you temperature,

humidity, DMX address and a

selection of error and status

messages.