Additional electrical specifications, Input conditions, Electrical characteristics – AMETEK XT Series User Manual

Page 19

Advertising
background image

Features and Specifications

Additional Electrical Specifications

17

Additional Electrical Specifications

Input Conditions

Electrical Characteristics

Voltage Mode Transient Response

Time

<100

μs recovery to 0.05% band, for ± 50%

load change in the range of 25% to 100% of

the rated load.

Time delay from power on until

output stable

1.5 s maximum

Output Noise and Ripple

1

1. RMS value measured at bandwidth of 20Hz to 300kHz, at the rear panel terminals; points of

measurement are the positive (+) and return (-) output terminal screws of the output terminal
block.

<1 mVrms (voltage mode)

<2 mArms (current mode)

Output Noise and Ripple

1

(250 V unit only)

<5 mVrms (voltage mode)

<1 mArms (current mode)

Standard AC Input Voltage

115 Vac ± 10%, 57-63 Hz

Option M1 (Factory installed)

110 Vac ± 10%, 47-63 Hz

Option AC220

220 Vac ± 10%, 47-63 Hz

Option AC230

230 Vac ± 10%, 47-63 Hz

Option AC240

240 Vac ± 10%, 47-63 Hz

AC Input Current at 115 Vac,

60 Hz

Single unit: 1.2 A

Dual unit: 2.4 A

Triple unit: 3.6 A

Quad unit: 4.8 A

Output Hold-up Time

approx. 10 ms at nominal line (full load)

Maximum Voltage Differential

from output to safety ground

±400 Vdc

Insulation Resistance

Input to chassis: >120 M

Ω

Output to chassis: >120 M

Ω

Isolation Voltage

(Output not to exceed ±400 Vdc

from chassis potential.)

Input to output: 1350 Vac

Advertising