AMETEK XT Series User Manual

Page 28

Advertising
background image

Load Connection and Sensing
Load Connection

28

Operating Manual for XT Series Power Supply

Load Wiring

To select wiring for connecting the load to the power supply, consider the following
factors:

insulation rating of the wire

current carrying capacity of the wire

maximum load wiring length for operation with sense lines

noise and impedance effects of the load lines

Insulation Rating

Use load wiring with a minimum insulation rating at least

equivalent to the maximum output voltage of the power supply. If the output is offset
from ground, the insulation must be rated at least for the sum of the supply’s
maximum output and the offset.

Current Carrying Capacity

As a minimum, load wiring must have a current

capacity greater than the output current rating of the power supply. This ensures that
the wiring will not be damaged even if the load is shorted. See Table 3.1 for the
maximum current rating, based on 450 A/cm

2

, for various gauges of wire rated for

105 °C operation. Operating at the maximum current rating results in an
approximately 30 °C temperature rise for a wire operating in free air. Where load
wiring must operate in areas with elevated ambient temperatures or bundled with
other wiring, use larger gauges or wiring rated for higher temperatures.

Table 3.1 Current Carrying Capacity for Load Wiring

Wire Size
(AWG)

Maximum Current
(A)

Wire Size
(AWG)

Maximum Current
(A)

20

2.5

6

61

18

4

4

97

16

6

2

155

14

10

1

192

12

16

1/0

247

10

21

2/0

303

8

36

Advertising