Installation, Mantel requirements, For qualified installers only) – Avalon Firestyles 864 See-Thru GS2 Installation User Manual

Page 41: Combustible mantels, Non-combustible mantels

Advertising
background image

Installation

(for qualified installers only)

41

© Travis Industries

4141208

100-01404

Mantel Requirements

Combustible Mantels

 Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured from the

face of the fireplace) must fall in the shaded portion of the table.

 Any material that protrudes more than 3/4” (19mm) from the non-combustible facing is considered a mantel

and must meet the mantel requirements.

Examples:

- If you wish to have an 8” (203mm) deep mantel, it must be at least 6-3/4” (171mm) above the fireplace face (44-3/4”, 1137mm above the base).
- If you wish to have a mantel 8” (203mm) above the fireplace face, it must be no deeper than 9” (229mm).

Non-Combustible Mantels

Non-combustible mantels must meet the clearances listed for combustible mantels. However, if you do wish to
reduce the clearances by using a non-combustible mantel, the following requirements must be met:

 Non-combustible

mantel

and facing must extend
from the top of the
appliance to the top
surface of the mantel.

 A

non-combustible

header must be used
(metal stud).

36-3/4"

933mm

a

b

Maximum Mantel Depth (b)

Mantel

Height

Above

Face (a)

0”

(25mm) 1"

(51mm) 2"

(203mm) 8"

(178mm) 7"

(152mm) 6"

(127mm) 5"

(102mm) 4"

(76mm) 3"

(229mm) 9"

0”

(254mm) 10"

(279mm) 11"

(305mm) 12"

(330mm) 13"

(356mm) 14"

(381mm) 15"

(406mm) 16"

(432mm) 17"

(457mm) 18+"

Base of the Fireplace

Combustible mantel columns (legs) that protrude

more than 3/4" (20mm) from the glass frame

must meet the sidewall clearance (1" (25mm)

from fireplace, 3-1/4" (83mm) from the glass

frame). If they protrude 3/4" (20mm) or less, they

must meet the facing clearance 2-1/4" (57mm)

from the glass frame.

Non-combustible mantel columns do not have a

minimum clearance.

Combustible Mantel

1" (25mm)

2" (51mm)

8" (203mm)

7" (178mm)

6" (152mm)

5" (127mm)

4" (102mm)

3" (76mm)

9" (229mm)

10" (254mm)

11" (279mm)

12" (305mm)

SIDE OF FIREPLACE

Drywall

Non-Combustible Mantel

Non-Combustible Framing (metal studs)

must be used for the header.

Non-Combustible Facing

Advertising