Installation – Avalon Firestyles Salish-1999 to 2000 User Manual

Page 12

Advertising
background image

12

Installation

(for qualified installers only)

Travis Industries

9 3 5 0 8 1 0 7

1 0 0 2 0 1

Approved Venting Configurations for Vertical Terminations with
Two 90¡ Elbows

¥

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
position.

0 feet

5 feet

10 feet

0 feet

0 feet

0 feet

NOTE:
Horizontal sections require a 1/4" rise
every 12" of travel.

Restrictor

Position # 3

16'(max)

8 feet (min.)

Restrictor

Position # 2

Restrictor

Position # 1

NOTE:
Restrictor positions are based
upon lab tests. The ideal restrictor
position may vary slightly,
especially when the termination is
near a demarkation line.

5 feet

10 feet

15 feet

20 feet

25 feet

30 feet

35' (max)

5 feet

10 feet

15 feet

20 feet

25 feet

30 feet

35' (max)

8 feet (min.)

5 feet

10 feet

16'(max)

Do not place an elbow directly off
the top of the heater.