ADDENDUM #2 Interior Masonry Chimney Conversions

¥

Follow the requirements and use the equipment listed in the illustration to the right to install this
appliance into an interior masonry chimney.

¥

Maximum vertical rise is 30'

¥

Minimum vertical rise is 10'

¥

Use the following restrictor positions:
Position 2 for heights between 8Õ and 12Õ
Position 3 for heights between 12Õ and 35'
NOTE: these restrictor positions are based upon lab tests. The ideal restrictor position may vary
slightly.

The entire chimney system
must be air-tight. Make sure to
seal the flashing, clean-out,
and thimble connection, and to
inspect the chimney.

#711 Flex Liner
(4Ó dia.)
(or other UL 1777
Gas Liner)

Co-Axial
Straight
Lengths

#991 High
Wind
Termination

#990 90¡ Elbow

Flashing
(included in
#934 Masonry
Conversion Kit

Make sure the coaxial pipe
maintains a 1Ó clearance to any
combustible. The vent must be
sealed air-tight.

High-Temp.

Silicone

Connector with
Cover (included
in #934
Masonry
Conversion Kit