BE1-50/51B-235/-236 General Information

1-1

SECTION 1 • GENERAL INFORMATION

INTRODUCTION

BE1-50/51B-235 and BE1-50/51B-236 protective relays are direct replacements for Westinghouse type

CO relays. The BE1-50/51B-235 has a 5-ampere current sensing input. The BE1-50/51B-236 has a

1-ampere current sensing input. Compatible Westinghouse model numbers are listed in Table 1-1.

Table 1-1. Westinghouse Relays Suitable for Direct Replacement

Catalog Number

Curve Type

CO-2∗11∗1N

Short Time

CO-5∗11∗1N

Long Time

CO-6∗11∗1N

Definite

CO-7∗11∗1N

Moderately Inverse

CO-8∗11∗1N

Inverse

CO-9∗11∗1N

Very Inverse

CO-11∗11∗1N

Extremely Inverse

Any digit covering all pickup ranges except 50 Hz models.

To replace an existing Westinghouse type CO, perform the following steps.

1. Select the desired relay settings on your new BE1-50/51B-235 or BE1-50/51B-236 relay.

2. Remove the existing ABB relay cradle.

3. Insert the new relay cradle.

4. Close the knife-blade switches.

5. Install the new Basler Electric cover and secure with the captive thumbnut.

BE1-50/51B-235 and BE1-50/51B-236 relays are self-powered, compatible with 50 or 60 Hz power

systems, and have three protection elements: one time overcurrent (51) element and two instantaneous

overcurrent (50) elements. The 51 element offers timing characteristic curves similar to those used by GE

IAC relays.

FEATURES

A wide range of pickup settings and front panel selectable time characteristics permit applications

involving coordination with fuses, reclosers, cold load pickup, motor starting, and fixed time requirements.

In addition, an integrating reset function is available to simulate the disk reset of electromechanical relays.
BE1-50/51B-235 and BE1-50/51B-236 overcurrent relays have the following standard features.

Independent time and instantaneous elements

A secure method to manually trip the breaker at the relay front panel

Direct reading front panel controls

Minimum pickup setting for safety during installation

Time characteristics extend to a pickup multiple of 40

Rugged draw-out construction

Gravity latching targets retain indication without power

Built-in accuracy eliminates internal adjustments

Minimum transient overreach

Field selectable characteristic curve selection similar to either GE IAC or Westinghouse CO type

curves

Field selectable instantaneous or integrating reset

Field selectable 50 or 60 Hz operation

Field selectable 0.0 or 0.1 second, fixed, instantaneous delay

Internal switches provide for selecting system-operating frequencies of 50 or 60 Hz, instantaneous

element delays of 0.0 or 0.1 second, characteristic curve group selection for either GE IAC or

Westinghouse CO type curves, and instantaneous or integrating reset characteristics. Switch location and

description is provided in Section 2.