9252000898 Rev B

BE1-50/51B-235/-236 General Information

1-3

Instantaneous Overcurrent A (50-A) Element

Setting Range:

2 to 99 Aac

BE1-50/51B-235 Pickup

Setting increment:

1 Aac

Accuracy:

Sum of ±2% and ±25 mAac

Setting Range:

0.4 to 19.8 Aac

BE1-50/51B-236 Pickup

Setting increment:

0.2 Aac

Accuracy:

Sum of ±2% and ±5 mAac

Dropout occurs at 95% of pickup value.

Dropout

Switch selectable—no intentional delay (SW3-2 OFF) or a fixed delay of 100 ms (SW3-2 ON). Appendix

A, Characteristic Curves illustrates the characteristic curve for the 50-A and 50-B elements.

Time Delay

Instantaneous Overcurrent B (50-B) Element

Setting Range:

1 to 15.9 Aac

BE1-50/51B-235 Pickup

Setting increment:

0.1 Aac

Accuracy:

Sum of ±2% and ±25 mAac

Setting Range:

0.2 to 3.18 Aac

BE1-50/51B-236 Pickup

Setting increment:

0.02 Aac

Accuracy:

Sum of ±2% and ±5 mAac

Dropout occurs at 95% of pickup value.

Dropout

Fixed at no intentional delay. Appendix A, Characteristic Curves illustrates the characteristic curve for the

50-A and 50-B elements.

Time Delay

Resets within 16 ms of when sensed current decreases below the pickup level.

Reset Characteristic

Current Sensing Input

Continuous Rating:

14 Aac∗

BE1-50/51B-235

1 Second Rating:

400 Aac

Continuous rating is 14 Aac for temperatures up to 45°C. See Figure 1-1 for derating curve.