BE1-50/51B-235/-236 Characteristic Curves

A-1

APPENDIX A • CHARACTERISTIC CURVES

INTRODUCTION

This appendix describes and defines the instantaneous overcurrent, time overcurrent, and integrating

time reset characteristics of the BE1-50/51B-235 and BE1-50/51B-236 relays.

INSTANTANEOUS OVERCURRENT CHARACTERISTICS

Timing
The instantaneous characteristic curves of the BE1-50/51B-235 and BE1-50/51B-236 relays are similar to

standard electromechanical instantaneous units. However, the time to trip for applications where the initial

sensing current is less than 400 mA may be slightly longer. This may occur on a very lightly loaded circuit

or when the relay is providing ground protection and is connected to measure neutral current. Figure A-1

shows the instantaneous characteristic curves for the maximum time to trip.

Figure A-1. Instantaneous Characteristic Curves

The delay of the Instantaneous A (50-A) element can be set for no intentional delay (switch SW3-2 open)

or a fixed delay of 100 ms (SW3-2 closed). Figure 2-2 illustrates the location of SW3. The time delay of

the 50-B element is not switch-selectable and is fixed at no intentional delay.

Pickup
The instantaneous elements of the BE1-50/51B-235 and BE1-50/51B-236 relays may be set lower than

the instantaneous element in Westinghouse CO relays and still have the same reach. This is because the

BE1-50/51B-235 and BE1-50/51B-236 instantaneous elements effectively eliminate the fault current

transient overreach components. When setting the BE1-50/51B-235 and BE1-50/51B-236 instantaneous

elements, calculate the symmetrical value without any adder for transient overreach.

TIME OVERCURRENT CHARACTERISTICS

Nine inverse time functions and one fixed (definite) time function can be selected at the front panel. Curve

types are identified by a letter designator. Available curve types are short inverse (S), long inverse (L),

definite time (D), moderately inverse (M), inverse (I), very inverse (V), extremely inverse (E), BS142

inverse, (B), and BS142 extremely inverse (C).