Be1-50/51b-236, Be1-50/51b-235 burden – Basler Electric BE1-50/51B-235 User Manual

Page 14

Advertising
background image

1-4

BE1-50/51B-235/-236 General Information

9252000898 Rev B

Figure 1-1. Current Sensing Input Derating Curve (BE1-50/51B-235)

Continuous Rating:

2.8 Aac∗

BE1-50/51B-236

1 Second Rating:

80 Aac

Continuous rating is 2.8 Aac for temperatures up to 45°C. See Figure 1-2 for derating curve.

Figure 1-2. Current Sensing Input Derating Curve (BE1-50/51B-236)

Figure 1-3

BE1-50/51B-235 Burden

illustrates the current sensing input burden characteristic.

At 0.5 Aac:

2.8 Ω

At 5.0 Aac:

0.3 Ω

Continuous Current

Current Sensing Input

0

2

4

6

8

10

12

14

16

-40

-20

0

20

40

60

Ambient Temperature (C)

Cu

rre

nt

(Aa

c)

Continuous Current

Current Sensing Input

0

0.4

0.8

1.2

1.6

2

2.4

2.8

3.2

-40

-20

0

20

40

60

Ambient Temperature (C)

Cu

rre

nt

(Aa

c)

Advertising
This manual is related to the following products: