Timing accuracy, Fixed time characteristic, Integrating time reset characteristic – Basler Electric BE1-50/51B-235 User Manual

Page 65: A-17

Advertising
background image

9252000898 Rev B

BE1-50/51B-235/-236 Characteristic Curves

A-17

Timing Accuracy
Timing accuracy is the sum of ±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times tap

and is for a given measured multiple of tap. Measurement accuracy of the multiple of tap is the sum of

±

2%, ±25 mA for the BE1-50/51B-235 and ±2%, ±5 mA for the BE1-50/51B-236.

Fixed Time Characteristic
The fixed time characteristic corresponds to the time dial setting and provides delays of 0.0 to 9.9

seconds. The time setting is constant over a range of pickup multiples from 1.0 to 40. Accuracy is ±1

cycle, ±2% of the time to trip for time dial settings of 0.1 and greater.

INTEGRATING TIME RESET CHARACTERISTIC

The relay can be user-configured for integrating or instantaneous type reset.
Integrating reset simulates the disk reset of electromechanical relays and begins when the current

decreases below 95% of pickup. BE1-50/51B-235 and BE1-50/51B-236 relays provide the integrating

reset function even when input current decreases to zero.
Integrating reset characteristics are defined by the following equation and are illustrated in Figure A-16.

See Table A-1 and A-2 for the equation constants.

1

2

=

M

RD

T

R

Where:

T

R

=

time to reset in seconds

R

=

constant for the particular curve

D

=

time dial setting

M

=

current in multiples of pickup setting during reset

Time characteristic curve equation:

Trip

to

Time

K

BD

C

M

AD

T

N

T

=

+

+

=

Where:

D

=

time dial setting

M

=

multiple of pickup setting

Reset characteristic curve equation:

Reset

to

Time

M

RD

T

R

=

=

1

2

Figure A-16. Integrating Reset Characteristic Curve