Be1-50/51b-236 burden, Frequency response, Transient response – Basler Electric BE1-50/51B-235 User Manual

Page 15: Frequency response -5, Transient response -5

Advertising
background image

9252000898 Rev B

BE1-50/51B-235/-236 General Information

1-5

Figure 1-3. Current Sensing Input Burden (BE1-50/51B-235)

Figure 1-4

BE1-50/51B-236 Burden

illustrates the current sensing input burden characteristic.

At 0.1 Aac:

57.0 Ω

At 1.0 Aac:

6.9 Ω

Figure 1-4. Current Sensing Input Burden (BE1-50/51B-236)

Frequency Response
A change of ±5 Hz from the nominal 50/60 Hz current causes <0.5% change in the current required for

pickup.

Transient Response
<10% overreach with system time constants up to 40 ms.

BE1-50/51B-230 CT Burden