9252000898 Rev A

BE1-50/51B-235/-236 Testing

i

SECTION 5 • TESTING

TABLE OF CONTENTS

SECTION 5 • TESTING ............................................................................................................................ 5-1

INTRODUCTION.................................................................................................................................... 5-1

DIELECTRIC TEST ............................................................................................................................... 5-1

TEST PROCEDURES ........................................................................................................................... 5-1

Model BE1-50/51B-235 (Five Ampere Sensing Input) ....................................................................... 5-1

Time Overcurrent (51) Pickup......................................................................................................... 5-1

Time Dial ......................................................................................................................................... 5-2

Integrating Reset ............................................................................................................................ 5-2

Instantaneous Overcurrent A (50-A) Pickup ................................................................................... 5-2

Instantaneous Overcurrent B (50-B) Pickup ................................................................................... 5-3

Target Indicators ............................................................................................................................. 5-4

Manual Trip ..................................................................................................................................... 5-5

Model BE1-50/51B-236 (One Ampere Sensing Input) ....................................................................... 5-6

Time Overcurrent (51) Pickup......................................................................................................... 5-6

Time Dial ......................................................................................................................................... 5-6

Integrating Reset ............................................................................................................................ 5-6

Instantaneous Overcurrent A (50-A) Pickup ................................................................................... 5-7

Instantaneous Overcurrent B (50-B) Pickup ................................................................................... 5-8

Target Indicators ............................................................................................................................. 5-9

Manual Trip ................................................................................................................................... 5-10

Figures
Figure 5-1. 51 Pickup, Time Dial, Integrating Reset, and 50-A Pickup Test Setup

.................................. 5-3

Figure 5-2. 50-B Pickup Test Setup

.......................................................................................................... 5-4

Figure 5-3. Target Indicator Test Setup

.................................................................................................... 5-5

Figure 5-4. 51 Pickup, Time Dial, Integrating Reset, and 50-A Pickup Test Setup

.................................. 5-8

Figure 5-5. 50-B Pickup Test Setup

.......................................................................................................... 5-9

Figure 5-6. Target Indicator Test Setup

.................................................................................................. 5-10