40036

RW

Atmospheric pressure unit selection.

40 = psig

41 = psia

42 = kPa g

43 = kPa a

44 = kg/sq cm g

45 = kg/sq cm a

46 = bar g

47 = bar a

40037

RW

Mode source selector.

0 = Digital

1 = Discrete

2 = Remote

40038

RW

Operating mode selector.

0 = Calibration mode

1 = Manual mode

2 = Automatic mode

40039

RW

Process variable selector.

1 = Liquid flow

2 = Upstream (P

1

) pressure

3 = Downstream (P

2

) pressure

4 = Delta pressure

5 = Temperature

6 = Gas flow

7 = Auxiliary 4-20 mA input

40040

RW

Controller action selector.

0 = Reverse acting

1 = Direct acting

40041

RW

Setpoint source selector.

0 = 4-20 mA input

1 = Digital

2 = Remote

40042

RW

Air action selector.

0 = Air-to-open

1 = Air-to-close

40043

RW

4-20 mA output selector.

0 = Position

1 = Liquid flow

2 = Upstream (P

1

) pressure

3 = Downstream (P

2

) pressure

4 = Delta pressure

5 = Temperature

6 = Gas flow

7 = Auxiliary 4-20 mA input

40044

RW

Proportional band for controller.

Range 1 to 9999. Percent

40045

RW

Derivative time for controller.

Range 0 to 9999. Minutes

40046

RW

Controller integral reset.

Range 0 to 9999. Repeats/minute