Flowserve StarPac II Control Valves User Manual

Page 52

Advertising
background image

Floating
Point
Register

Attribute Description

Notes

70521

RO

Signature/Logger auxiliary 4-20 mA input
data in percent.

This value is loaded from device when the
load signature data flag or load data
logger data flag is set to 1. (Registers No.
40084, No. 40085)

70523

RO

Logger setpoint data in percent.

This value is loaded from device when the
load data logger data flag is set to 1.
(Register No. 40085)

70525

RO

Logger process variable data in percent. This value is loaded from device when the

load data logger data flag is set to 1.
(Register No. 40085)

70527

RW

Calibration offset for minimum process
temperature.

Range -1.0E4 to 1.0E4. Used as
calibrated minimum temperature.

70529

RW

Positioner deviation range.

Range .1 to 100. Device will set the alarm
status bit (Positioner deviation) when the
difference between position Hallpot output
and I/P input is greater than this value.

70531

RW

Positioner change percentage over one
second.

Range .1 to 100. Device will set the alarm
status bit (Positioner deviation) when the
position percentage does not follow the I/P
percentage in one second.

70533

RW

Loss of supply air pressure ramp rate in
percent/minute.

Range 0 to 1.0E6. Rate at which the
valve will close on loss of air supply
pressure.

70535

RW

Supply pressure in psig.

Range 0 to 200.

70537

RO

Setpoint data in percent.

70539

RO

Process variable in percent.

70541

RW

Viscosity A coefficient

70543

RW

Viscosity B coefficient

70545

RO

Viscosity Correction Factor

70547

RO

Alarm state as floating point variable

70549

RW

Remote mode change register

70551 RW

Remote

command

70553

RO

Totalized liquid flow (user units)

70555

RO

Totalized gas flow (user units)

70557

RO

Cylinder top pressure (psig)

70559

RO

Cylinder bottom pressure (psig)

70561

RW

user units = 20mA at AI #2

70563

RW

user units = 4mA at AI #2

70565

RO

AI #2 (user units)

70567

RW

User flow unit multiplier

Greater than zero

70569 to
70575

N/A

Floating point expansion space.

70577

RO

Positioner Command (%)

StarPac II User Interface Manual

46

Advertising