Integer
Register

Attribute Description

Notes

40094

RW

Variable number for liquid flow scaling
factor input to be used in flow
calculation.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
use the value from that variable as the
liquid flow scaling factor input to the flow
calculation; -1 disables.

40095

RW

Variable number for gas flow scaling
factor input to be used in flow
calculation.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
use the value from that variable as the gas
flow scaling factor input to the flow
calculation; -1 disables.

40096

RW

Variable number of output No. 1 to be
displayed on Local display.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on
LCD display; -1 disables.

40097

RW

Variable number of output No. 2 to be
displayed on Local display.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.

40098

RW

Variable number of output No. 3 to be
displayed on Local display.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.

40099

RW

Variable number of output No. 4 to be
displayed on Local display.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.

40100

RW

Variable number of output No. 5 to be
displayed on Local display.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.

40101

RW

Variable number of output No. 6 to be
displayed on Local display.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.

40102

RW

Variable number of output No. 7 to be
displayed on Local display.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.

40103

RW

Variable number of output No. 8 to be
displayed on Local display.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.

40104

RW

Variable number of output No. 9 to be
displayed on Local display.

Range -1 to 1023. Writing a value in the
specified range will cause the device to
display the output from that variable on the
LCD display; -1 disables.

StarPac II User Interface Manual