Integer
Register

Attribute Description

Notes

40047

RW

Scaled setpoint command.

Range 0 to 9999, with fixed scale range -
12.5 to 112.5 percent.

40048

RW

Scaled digital command.

Range 0 to 9999, with fixed scale range -
12.5 to 112.5 percent.

40049

RW

Flow type indicator.

0 = Liquid

1 = Gas

40050

RW

Positioner signal source selector.

0 = Direct 4-20 mA

1 = Digital

40051

RW

Analog command signal state selector.

0 = Normal

4 mA = 0% command

20 mA = 100% command

1 = Inverted

4 mA = 100% command

20 mA = 0% command

40052

RW

Loss of analog command signal hold
time.

Range 0 to 9999. Seconds

40053

RW

Interval between data logger data points. Range 0 to 9999. Seconds

0 = Data logger inactive.

40054

RW

Actuator bottom pressure transducer
minimum calibrated ADC value
corresponding to 0 psig.

Range -32768 to 32768

40055

RW

Actuator bottom pressure transducer
maximum calibrated ADC value
corresponding to supply pressure psig.

Range -32768 to 32768

40056

RW

Actuator top pressure transducer
minimum calibrated ADC value
corresponding to 0 psig.

Range -32768 to 32768

40057

RW

Actuator top pressure transducer
maximum calibrated ADC value
corresponding to supply pressure psig.

Range -32768 to 32768

40058

RW

Minimum ADC value corresponding to
calibrated 4 mA command input.

Range 0 to 16384

40059

RW

Maximum ADC value corresponding to
calibrated 20 mA command input.

Range 0 to 16384

40060

RW

Output to I/P.

Range 0 to 65535. If system is not in
Calibration mode, writing to this register
will not have an effect.

40061

RW

Minimum DAC value corresponding to
0% position.

Range 0 to 65535.

40062

RW

Maximum DAC value corresponding to
100% position.

Range 0 to 65535.

40063

RW

Minimum ADC value corresponding to
0 °F ambient temperature.

Range -32768 to 32768