Integer
Register

Attribute Description

Notes

40064

RW

Maximum ADC value corresponding to
185 °F ambient temperature.

Range -32768 to 32768

40065

RW

Minimum ADC value corresponding to
4 mA on the auxiliary input channel.

Range 0 to 16384

40066

RW

Maximum ADC value corresponding to
20 mA on the auxiliary input channel.

Range 0 to 16384

40067

RW

Output from analog output channel.

Range 0 to 65535. If system is not in
Calibration mode, writing to this register
will not have an effect.

40068

RW

Minimum DAC value corresponding to
4 mA on analog output channel.

Range 0 to 65535.

40069

RW

Maximum DAC value corresponding to
20 mA on analog output channel.

Range 0 to 65535.

40070

RW

Minimum ADC value corresponding to
0 psig process pressure on upstream
pressure (P

1

) transducer.

Range -32768 to 32768

40071

RW

Maximum ADC value corresponding to
maximum psig process pressure on
upstream pressure (P

1

) transducer.

Range -32768 to 32768

40072

RW

Minimum ADC value corresponding to
0 psig process pressure on downstream
pressure (P

2

) transducer.

Range -32768 to 32768

40073

RW

Maximum ADC value corresponding to
maximum psig process pressure on
downstream pressure (P

2

) transducer.

Range -32768 to 32768

40074

RW

Minimum ADC value corresponding to
0% open from position Hallpot output.

Range -32768 to 32768

40075

RW

Maximum ADC value corresponding to
100% open from position Hallpot output.

Range -32768 to 32768

40076

RW

Minimum ADC value corresponding to
calibrated minimum temperature in °F.

Range 0 to 16384.

40077

RW

Maximum ADC value corresponding to
calibrated maximum temperature in °F.

Range 0 to 16384.

40078

RW

Totalizer reset flag.

Range 0 to 1. Writing a value of 1 to this
register causes the device to reset the
totalized flow and time.

40079

RW

Read real-time clock flag.

Range 0 to 1. Writing a value of 1 to this
register causes the device to load the real-
time clock information into real-time string.
(Register No. 50625)

40080

RW

Set real-time clock flag.

Range 0 to 1. Writing a value of 1 to this
register causes the device to set the real-
time clock from the real-time string.
(Register No. 50625)