String Registers


The register numbers in this table are not consecutive because of the varying length of each string in this
area of StarPac memory. Most of these strings are available as RW strings; however, we suggest that you
only write to 50617 (TAGNAME) and 50625 (Real time and date) and leave the others as they are because
that information is factory set.

Trying to access the middle of a string will result in an exception response from the device.

String
Register

Attribute Description

Notes

50601

RO

Embedded software version number.

ASCII characters. 16 bytes

50609

RW

Valve serial number.

ASCII characters. 16 bytes.

50617

RW

Tag name for current device.

ASCII characters. 16 bytes.

50625

RW

Real time and date information.

ASCII characters. 32 bytes. This string is
used to reset internal clock when the real
time write flag (Register No. 40080) is set
to 1.

50641

RW

LCD display descriptors.

ASCII characters. 64 bytes. Segmented
into 12 5 byte strings.

50673

RW

LCD display units.

ASCII characters. 64 bytes. Segmented
into 12 5 byte strings.

50705

RO

Device descriptor.

Initialized at factory with "StarPac II."

50713

RO

Logger real time and date data.

This string is loaded from device when
the load data logger data flag is set to 1.
(Register No. 40085)

50729

RW

Trim number of this system.

ASCII characters. 16 bytes.

50737

RW

Trim characteristics of this system.

ASCII characters. 16 bytes.

50745

RW

Trim type of this system.

ASCII characters. 16 bytes.

50753

RW

Pressure class of this system.

ASCII characters. 16 bytes.

50761

RW

Valve model.

ASCII characters. 16 bytes.

50769

RW

Flow direction.

ASCII characters. 16 bytes.

50777

RW

Valve body size of this system.

ASCII characters. 16 bytes.

50785

RW

Valve body material of this system.

ASCII characters. 16 bytes.

50793

RW

Packing style used in this system.

ASCII characters. 16 bytes.

50801

RW

Packing used in this system.

ASCII characters. 16 bytes.

50809

RW

Gasket material used for this system.

ASCII characters. 16 bytes.

50817

RW

Actuator size used on this system.

ASCII characters. 16 bytes.

50825

RW

Spring used in actuator on this system.

ASCII characters. 16 bytes.

StarPac II User Interface Manual