Flowserve StarPac II Control Valves User Manual

Page 48

Advertising
background image

Floating
Point
Register

Attribute Description

Notes

70331

RW

Antoine B fluid coefficient.

Range 0 to 1.0E6. Used to calculate the
fluid vapor pressure.

70333

RW

Antoine C fluid coefficient.

Range -1.0E4 to 1.0E4. Used to calculate
the fluid vapor pressure.

70335

RW

Local atmospheric pressure.

Range 0.1 to 1000. psig. Any
conversions will have to be done by
external software.

70337

RW

Liquid flow multiplier.

Range 0.1 to 100. Used to scale the liquid
flow value.

70339

RW

Gas flow multiplier.

Range 0.1 to 100. Used to scale the gas
flow value.

70341

RW

Fluid critical pressure.

Range .1 to 1.0E5.

70343

RW

Fluid critical temperature

Range .1 to 1.0E5.

70345 RW

Fluid

F

K

coefficient.

Range 0 to 10.

70347

RW

Fluid molecular weight.

Range 0 to 1.0E3.

70349

RW

Fluid reference temperature in °R.

Range .1 to 1.0E4.

70351

RW

Fluid specific gravity at reference
temperature.

Range 1.0E-3 to 100.

70353

RW

Calculated calibration slope for I/P input. Range -1.0E9 to 1.0E9.

70355

RW

Calculated calibration slope for ambient
temperature sensor.

Range -1.0E9 to 1.0E9.

70357

RW

Calculated calibration slope for 4-20 mA
auxiliary input channel.

Range -1.0E9 to 1.0E9.

70359

RW

Calculated calibration slope for upstream
(P

1

) process pressure transducer.

Range -1.0E9 to 1.0E9.

70361

RW

Calculated calibration slope for
downstream (P

2

) process pressure

transducer.

Range -1.0E9 to 1.0E9.

70363

RW

Calculated calibration slope for position
Hallpot output.

Range 1.0E-9 to 1.0E6.

70365

RW

Calculated calibration slope for process
temperature thermocouple output.

Range 1.0E-9 to 1.0E6.

70367

RW

Calculated calibration slope for 4-20 mA
analog output channel.

Range 1.0E-9 to 1.0E6.

70369

RW

Offset for DPISA calculation.

Range 0 to 100.

70371

RW

Design stroke of valve.

Range .001 to 100.

70373

RW

Gas A1 coefficient used in gas flow
calculation.

Range -1000 to 1000.

70375

RW

Gas A2 coefficient used in gas flow
calculation.

Range -1000 to 1000.

70377 RW

C

V

A1 curve fit coefficient.

Range -1.0E9 to 1.0E9.

70379 RW

C

V

B1 curve fit coefficient.

Range -1.0E9 to 1.0E9.

70381 RW

C

V

C1 curve fit coefficient.

Range -1.0E9 to 1.0E9.

StarPac II User Interface Manual

42

Advertising