Menus of Inputs/ Outputs

– con tinued –

LRG 16-40 calibration

1.

In the menu

LRG 16-40 CAN 1...10

press

.

2.

Use button

Compensation On/Off

to acti-

vate or de-activate the temperature com-
pensation. All indicated readings are here
absolute readings of the current conductiv-
ity.

3.

To carry out an autoscan press button

Au-

toscan

. The auto-curve temperature com-

pensation is suitable for boilers operating
with variable pressure, which means that
the boiler does not have a fixed working
pressure (e. g. low load 10 bar, full load 15
bar). The system detects in steps of 10 °C
all temperature and conductivity values from 100 °C to the service temperature. For
this purpose the boiler must reach its working pressure (with variable pressure oper-
ation: max. allowable working pressure). If the standard curve is not suitable for var-
iable pressure operation, use can be made of the recorded curve.

4.

If you want to use the autoscan values, e. g. because the standard curve is not suit-
able, press button

Auto activ.

. The previously recorded auto-curve will be activated.

The auto-curve can be overwritten by a newly recorded curve at any time.

5.

To adjust the standard-curve temperature compensation click in the green input field.
The menu

Select standard curve

appears. The standard curve temperature com-

pensation is suitable for boilers operating with variable pressure, which means that
the boiler does not have a fixed working pressure (e. g. low load 10 bar, full load 15
bar). The standard curves of feedwater conditioning agents with different basic con-
ductivities compensate for the influence of the temperature on readings within the op-
erating range.

6.

To adjust the linear temperature compensation click in the input field next to the but-
ton

Linear

. The menu

Select temperature coefficient

appears. The gradient (de-

fault setting: 2.1%/°C) is normally used for steam boilers operating with constant
pressure. The conductivity is ascertained at an ambient temperature of 25 °C. The
cell constant can be modified in order to calibrate the value measured by the elec-
trode. The gradient can be verified at operating pressure with the aid of a calibrated
conductivity meter.

7.

Click in the green input field to enter the cell constant C of the conductivity electrode
(values must be within the admissible range).

8.

Use the on-screen keyboard to overwrite or modify the value in the input mask.

LRG 16-40

Calibration

Logo

0.000

Auto activ.

Cell constant

Autoscan

Standard curve

Linear

Compensation Off