Controller Menu

– continued –

Controller setup

- contin ued -

6.

Use the three controller buttons to activate the controller. An activated controller is
visually indicated in the menu

Controller

.

7.

Use button

Off

to de-activate the controller.

8.

If no controller type has been selected, the status indicator indicates Off. If a control-
ler has been selected, the respective button is highlighted in yellow and the status
indicator indicates On.

9.

To configure the controller press button

Continuous controller

, button

2-pos. con-

troller

or button

3-pos. controller

.

Continuous controller setup

1.

Press button

Continuous controller

in the menu

Controller Setup

.

2.

The name of the controller is highlighted in
yellow.

3.

The green input field

Actual value

shows

the actual value. Click in the input field to
show all established signals.

4.

Select the signal that indicates the re-
quired parameters. For more information
on the setup and configuration of the
equipment see menu CAN Input and Ana-
log Input.

5.

The green input field

Setpoint

shows the

setpoint element. The setpoint can be adjusted directly in the equipment or external-
ly, e. g. via a potentiometer.

6.

To toggle between internal and external setpoint press button

Internal setpoint

/

Ex-

ternal setpoint

.

7.

To enter the signal for an external setpoint click in the green input field. All estab-
lished sensing elements will be indicated.

8.

Select the signal that indicates the required parameters. For more information on the
setup and configuration of the equipment see menu CAN Input and Analog Input.

9.

The green input field

Manip. variable

shows the manipulated variable element. To

select a signal for the manipulated variable click in the green input field. All adjusted
signals will be indicated.

10. Select the signal to which the manipulated variable shall be sent.

You will find the settings in the menu Analog Outputs.

Continuous

controller setup

Logo

MAX limit

Offset

MIN limit

NC

NC

NC

NC

Position

Manip. variable

Actual value

Controller 1

Int. setpoint