Menus of Inputs/ Outputs

– con tinued –

Analog input 1...10 setup

1.

In the menu

Analog Input 1...10

press

.

2.

The menu

Analog Input 1...10 Setup

is

password protected. Press

and enter

your password.

3.

To select the type of sensor press button
Type. The available types of sensor are
shown in a list.

4.

To activate or de-activate the analog input
press button

AI On/Off

.

5.

To select the unit of the measured value
click in the green input field.

6.

Use the on-screen keyboard to overwrite or modify the unit in the input mask.

7.

To name the analog input click in the input field Name.

8.

Use the on-screen keyboard to overwrite or modify the value in the input mask.

9.

To change the range limits click in the corresponding input field. First establish the
0% -100% range and then enter further values.

10. Use the on-screen keyboard to overwrite or modify the value in the input mask.

AI 1

Setup

Logo

PT100

Name

Off

Range 100%

PT 100

Range 0%

Unit

Type

AI On

0.00

0.00

0.00

0.00

0.00

0.00

Note

The HiHi and LoLo settings can be used for alarms and the Hi and Lo settings
for switchpoints of 2-position controllers.

The alarm monitoring function is de-activated when all HiHi to LoLo values
have been set to 0%.