Element continuous/3-position controller, Controller menu – Flowserve SPECTORcontrol User Manual

Page 59

Advertising
background image

59

Controller Menu

– continued –

3-element 3-position controller setup

- contin ued -

14. The green input field

Offset

shows the current value. To enter or change a value click

in the input field.

15. The adjusted value appears in the input mask. Use the on-screen keyboard to over-

write or modify the value.

16. The green input fields

Min/Max limit

show the current limit values. To enter or

change a value click in the input field.

17. The adjusted value appears in the input mask. Use the on-screen keyboard to over-

write or modify the value.

18. The green input fields

Min. pulse

and

Valve run time

show the current values. To

enter or change a value click in the input field.

19. The adjusted value appears in the input mask. Use the on-screen keyboard to over-

write or modify the value.

3-element continuous/3-position controller

1.

Press button

Parameterised as

in the menu

3-element controller

.

2.

The menu is protected by password. Press
button

and enter your password.

3.

The values of the steam flowrate and the
water flowrate are highlighted in yellow.
Below that the current level, the status in-
dicator

Enabled/Disabled

and the adjust-

ed controller are shown. Next to these
values the setpoint and the current control-
ler setting are indicated.

4.

To change the internal setpoint click in
the green input field.

Note

The MIN and MAX limit values specify the admissible manipulated variable
range of the controller.

Controlled actual value = Level - (steam flowrate - water flowrate) x rating
if steam flowrate – water flowrate > 0.

If the steam or water flowrate signal is faulty, the controller will only use the
actual value of the level.

3-element

3-pos. controller

Logo

Water flowr.

Int. setpoint

Position

Steam flowr.

Level

Disabled

NC

0.0

0.00

0.00

0.0

0.0

0.00

0

0