Controller Menu

– continued –

3-element 3-position controller setup

1.

Press button

3-pos. controller

in the menu

3-element controller setup

.

2.

The name of the controller is highlighted in
yellow.

3.

The green input fields

Steam flowrate

,

Water flowrate

and

Level

show the ad-

justed signals. Click in the input field to
show all established signals.

4.

Select the signal that indicates the re-
quired parameters. For more information
on the setup and configuration of the
equipment see menu

CAN Input

and

An-

alog Input

.

5.

The green input field

Rating

shows the adjusted value. To change the value click in

the input field. The value rates the influence of the difference between steam and wa-
ter flowrate on the measured level signal.

6.

The current value appears in the input mask. Use the on-screen keyboard to over-
write or modify the value.

7.

To toggle between internal and external setpoint press button

Internal setpoint

/

Ex-

ternal setpoint

.

8.

To enter the signal for an external setpoint click in the green input field. All estab-
lished sensing elements will be indicated.

9.

Select the signal that indicates the required parameters. For more information on the
setup and configuration of the equipment see menu

CAN Input

and

Analog Input

.

10. The green input field

Position

shows the position indicator. To select a position feed-

back signal click in the green input field. All adjusted signals will be indicated.

11. Select the signal that indicates the required parameters. For more information on the

setup and configuration of the equipment see menu

CAN Input

and

Analog Input

.

12. The green input field

On

and

Off

shows the adjusted signal receiver. Click in the input

field to show all established signals.

13. Select the digital output that shall be activated. You will find more information on

equipment setup in the menu Digital Outputs.

3-elem. 3-pos.

Controller setup

Logo

NC

Name

Steam flowrate

Water flowrate

Rating

Level

Int. setpoint

NC

NC

NC

NC

0.000 %