ELECTRICAL CONNECTION INSTRUCTIONS

8.3

Electrical Loads

When connected to a subcircuit protected by a circuit breaker, the current drawn by an oven may cause the
cuircuit breaker to trip in some cases. It is recommended that the following installation procedures are used.

Model

kW Rating

Maximum Current

Recommendation

(Amperes)

Cable Size

Circuit Breaker

FED

10.0

42

4.0 mm

2

45 Amp

FE90

4.8

20

2.5 mm

2

25 Amp

MULTI-FUNCTION OVEN

FED

FE90

NORMAL OVEN

2400W

3000W

FAN OVEN

2200W

2200W

GRILL

2700W

3500W

FAN & LIGHT

200W

100W

WARMER DRAWER

500W

500W

BBQ GRILL

2800W

SMALL HOTPLATE

MED HOTPLATE

LARGE HOTPLATE

RIGHT HAND OVEN

OVEN

2400W

GRILL

2700W

TOTAL

10.0 kW

4.8 kW

55