M40DV-CR/CL Corner Gas Fireplace

Installation

Installing The Fireplace Shell

The fireplace may be installed in any location that maintains clear-
ances to air conditioning ducts, electrical wiring and plumbing. Safety,
as well as efficiency of operation, must be considered when selecting
the fireplace location. Try to select a location that does not interfere
with room traffic, has adequate ventilation, and offers an accessible
pathway for Direct Vent installation.
The fireplace dimensions are shown below:

Figure 1. Fireplace dimensions.

Framing

Unprotected combustible walls which are perpendicular to the
fireplace opening, must not project beyond the shaded area shown in
Figure 20b.
For protection against freezing temperatures, it is recommended that
outer walls of the chase be insulated with a vapour barrier. This will
reduce the possibility of a cold-air convection current on the fireplace.

Figure 2a. Framing dimensions.

Clearances

The

M40DV-CR/CL clearances to combustible materials are:

Top*

8"

Rear

1½"

Closed Side

1½"

Floor

Combustible

Mantle**

6"

Flue Cover

1/2"

* Clearance from the top of the fireplace to

a combustible ceiling within the fireplace
enclosure.

** Refer to page 12.

End View

Top View

Front View

Figure 2b. Flue Cover clearances to combustibles when installing

the unit in a top vent configuration.

38”

41”

24”

40”

WARNING!

When this appliance is installed directly on carpeting, tile or any
combustible material other than wood flooring, it must be installed
on a metal or wood panel extending the full width and depth of
the appliance.