P/N XG0206

M40DV-CR/CL Corner Gas Fireplace

Installation

Vertical Vent Installations

Vertical Installations with a rise greater than 12' can be reduced
from 5/8 to 4/7 venting.

minimum 2' (two feet) above the highest point where

vent passes through the roof.

minimum 6' (six feet) from a mechanical air inlet

minimum 18" (1 1/2 feet) from a parapet wall.

Maximum vent height is 30 feet above fireplace.

Note: Flame characteristics will change if the maximum vent

height is used.

Minimum clearance to combustible construction around the

vent pipe is 1" on all sides must be maintained, except on hori-

zontal venting where the

top of the pipe must have a clearance of

at least 2".

2. Offset Vertical Installations

A maximum of two offsets

(each offset has two 90° bends) may be

made if the length of the offsets does not exceed 25% of the vertical
vent height, when measured center to center of piping.

Example:

Typical vent installation.

30' vertical vent

2 - 2' offsets required

25% of 30' = 7-1/2' max. offset allowed

This venting configuration meets requirements.

Figure 10b. Vertical venting with 2 offsets (1 offset= two 90° bends).

* If reducing to 4"/7" venting see figure 19.

Figure 10a. Vertical venting with 1 offset (1 offset= two 90° bends).

* If reducing to 4"/7" venting see figure 19.

1. Straight Vertical Installation

Figure 9. Straight, vertical venting. When the vent run is not reduced

use a PEL-90F/F elbow, which is connected directly to the

fireplace flue collar. In this case, the PXT-10 adaptor is not

needed. * If reducing to 4"/7" venting see figure 19.