MOVINCOOL 24HFU / 24HFU-1 SERVICE

PAGE 14

ELECTRICAL SYSTEM • 24HFU

4-2.

Control Box

4-2-1.

Capacitor

The capacitor is used to boost power
output to the fan motor and the compres-
sor at start-up.
The specifications of each capacitor are
shown below.

Circuit of Auxiliary Relay

Auxiliary Relay

4-2-2.

Auxiliary Relay

This auxiliary relay is normally closed
when the unit is in operation (FAN or
COOL), and supplies power to the com-
pressor relay and the fan motor. In the
following cases, however, the relay opens
to interrupt power to the compressor and
the fan motor.
• When the drain tank is filled with water.

(Drain switch OFF.)

• When the high pressure becomes

excessively high. (High pressure switch
OFF.)

When current flows across A and B,
terminals 11 and 12, 13 and 14, 15 and
16, 19 and 20 conduct.

Specifications:

Rated Voltage

AC 240V

Rated current

15 amps

UL Listed File No.

E112482

Capacitor

Registrant Voltage

Capacitance

(Volt)

(mF)

For fan motor

440

12.5

For compressor

370

40

4-2-3.

Compressor Relay

The compressor relay is closed when the
unit is operating in COOL mode, and
supplies power to the compressor. How-
ever in the following cases, the relay
opens to cut off power to the compressor.
• When the auxiliary relay is opened.

(Drain switch OFF or high pressure
switch OFF.)

• When the evaporator has frosted.

(Thermostat OFF.)

Specifications:

Rated Voltage

AC 230V

Rated Current

30 amps

UL Listed File No.

E43028

Circuit of Compressor Relay