24hfu-1 – MovinCool 24HFU Service Manual User Manual

Page 39

Advertising
background image

MOVINCOOL 24HFU / 24HFU-1 SERVICE

PAGE 39

REPAIR - INSPECTION AND REPAIR OF ELECTRICAL SYSTEM • 24HFU-1

UNIQUE FEATURES OF MODEL 24HFU-1

4-1.

Inspection of Time Delay Relay

Check for continuity between terminals 1 and 9, and 4 and 12. Continuity should exist.
With rated voltage applied at terminal 13 and 14 (and after a time delay of 75 seconds) continuity should
exist between terminals 5 and 9, and 8 and 12. Delay time 75

±

15 seconds.

If continuity does not exist as specified, replace the time delay relay.

24HFU-1

Inspection of Time Delay Relay

4-2.

Inspection of Restart Auxiliary Relay

Check for continuity between terminals 1 and 5. Continuity should exist.
With rated voltage applied at terminals 7 and 8, continuity should exist between terminals 3 and 5.
If continuity does not exist as specified, replace the restart auxiliary relay.

Inspection of Restart Auxiliary Relay