MOVINCOOL 24HFU / 24HFU-1 SERVICE

PAGE 48

REPAIR - REASSEMBLY

Reassemble the unit in the reverse order of removal.
Described below are the parts that require special care
in reassembling the unit. Perform all wiring or rewiring
as referenced in the wiring diagram.

6-1.

Compressor Mounting

Mount the compressor on the frame, using
cushions, steel collars, spring washers, plate
washers and nuts.

6-2.

Blower Assembly

Install blower fans (for evaporator and con-
denser).

Tightening torque:
1.3

±

0.26 lb-in (1.5

±

0.3kg-cm)

NOTE

After reassembling, the gap between blower fan
and housing should be 0.06 inches (1.5 mm) or
more.

Compressor Mounting

6-3.

Wiring Notice

Secure the wires using clamps so that they do
not come into contact with the edges of the
structure, etc. Secure the wires using clamps in
the same position they were before removal.

6-4.

Perform the inspection of cooling capacity
and check for abnormal noise or abnormal
vibration.

Blower Assembly Mounting