24hfu – MovinCool 24HFU Service Manual User Manual

Page 36

Advertising
background image

MOVINCOOL 24HFU / 24HFU-1 SERVICE

PAGE 36

REPAIR - INSPECTION AND REPAIR OF ELECTRICAL SYSTEM • 24HFU

4-2.

Inspection of Control Switch

At each position of the control switch, there
should be continuity across the following
terminals.

Switch Position Conducting Terminals

OFF

2 - 5

FAN

1 - 5

COOL

1 - 5, 4 - 5

If there is no switch continuity, replace the
control switch.

Inspection of Control Switch

4-3.

Inspection of Capacitor (for Fan Motor and
Compressor)

Set the ohmmeter to 100 KW range. Place two
probes against the two terminals of the capaci-
tor. At first, the ohmmeter should indicate 0

,

then the meter reading should gradually ap-
proach infinity. If the ohmmeter indicates infinity
from the first or the meter reading fails to move
from 0

, replace the capacitor.

Inspection of Capacitor

4-1.

Inspection of Auxiliary Relay

Check for continuity across the terminals when
the test button is depressed and when it is
released.

Inspection of Auxiliary Relay

Terminals

State of Reset Switch

Continuity

11-12

Depressed

Conduct

Released

Not Conduct

13-14

Depressed

Conduct

Released

Not Conduct

15-16

Depressed

Conduct

Released

Not Conduct

19-20

Depressed

Conduct

Released

Not Conduct

Measure the resistance across terminals
A and B. Standard resistance: 1900~2100

When the resistance is out of this range, replace
the auxiliary relay.

24HFU

WARNING

Before and after testing the capacitor for the fan
motor and compressor, proper discharging of
electrostatic charge should be performed by a
qualified service technician. Improper discharge
of the capacitor can cause electrical shock or
death.