MOVINCOOL 24HFU / 24HFU-1 SERVICE

PAGE 27

REPAIR - TROUBLESHOOTING

TROUBLE

SYMPTOM

POSSIBLE CAUSE

REMEDY

Unit does

Unit does

1) Defective control switch

Refer to 4-2

not operate

not operate

2) Defective auxiliary relay

Refer to 4-1

3) Defective drain switch

Refer to 4-5

Unit starts,

1) Defective overload relay

Refer to Wiring Diagram

but stops

2) Defective fan motor

Refer to 4-6

immediately

3) Defective compressor motor

Refer to 4-7

Unit operates,

1) Defective compressor motor

Refer to 4-7

but stops after

2) Defective overload relay

Refer to Wiring Diagram

a few minutes

3) Defective high pressure switch

Refer to 4-10

Water leakage

1) Defective drain pan (crack or hole)

Repair

from the unit

2) Defective drain hose

Repair or replace

(clogged or loose connection)

Before troubleshooting this system, the following inspection should be performed.

1-1.

Inspection of Power Source Voltage

Check the voltage of the power source.
24HFU & 24HFU-1: Single phase 230 volts (60Hz)
Check the operation and condition of the fuse or circuit breaker in the power source.

1-2.

Inspection of Air Filters

Remove the air filters and check the element. If it is dirty, wash it as described in the OPERATION
MANUAL supplied with the unit.

1-3.

Inspection of Drain Tank

Be sure tank is fully drained.
The following chart is provided as a guide for categorized problem remedies. Detailed information is
contained in the OPERATION MANUAL supplied with the unit.

Abnormal

1) Loose compressor mounting nut

Tighten

noise and

2) Deformed or worn rubber grommet

Replace

shaking

on the compressor mounting bolt
3) Interference with other materials.

Remove it

4) Interference of fan and scroll

Readjust

Insufficient

1) Clogged spine fin and/or air filter

Refer to 2-1 and/or

velocity of

wash the air filter

cooled air

2) Defective fan motor

Refer to 4-6

3) Defective fan motor capacitor

Refer to 4-3

Insufficient

Compressor and

1) Abnormal environment condition

Refer to 2-2

cooling

fan motor rotate

2) Clogged spine fin

Refer to 2-1

properly

3) Leak in system

Refer to 5-1

4) Clogged refrigerant system

Refer to 5-1

Compressor motor 1) Defective compressor motor

Refer to 4-7

does not rotate

2) Defective compressor capacitor

Refer to 4-3

3) Defective auxiliary relay

Refer to 4-1

4) Defective control switch

Refer to 4-2

5) Defective overload relay

Refer to Wiring Diagram

6) Defective wiring connection

Check and correct

7) Defective thermostat

Refer to 4-9

8) Defective compressor relay

Refer to 4-11

Cooled air

Blower motor does 1) Defective fan motor

Refer to 4-6

does not

not rotate

2) Defective fan motor capacitor

Refer to 4-3

come out

3) Defective wiring connection

Refer to 4-8

4) Defective auxiliary relay

Refer to 4-1

TroubleShooting Chart