ONICON Turbine Flow Meter

Factory Installed Cable

ONICON turbine flow meters are provided with a variety of output signals. Only the red,

green and black wires are required to power the flow meter and operate the display. For

bi-directional applications, the gray and violet wires are also required to indicate flow

direction.

* 24VDC Supply + (Red)
* Supply Common - (Black)

* Frequency + . (Green)

(A) Direction + (Grey)
(A) Direction - (Violet)

(B) Top Turbine (White)

(B) Bottom Turbine (Orange)

F-1100, F-1200 & F-1300 Series

Flow Meter Connections

Connections shown with * are
required for all models.

Connections shown with (A)

are required for all

bi-directional models.

Connections shown with (B)

are required for all dual turbine models,

including bi-directional.

(C or D) 4-20mA + (Blue)
(C or D) 0-10 VDC + (Brown)

(E) Scaled + (Blue)
(E) Scaled - (Brown)

For F-1x10, F-1x11 & F-1x30

Flow Meter Inputs

(C) Analog Common - (Black)

* Shield

Auxiliary Flow Meter Signals

Connections shown are for flow meter

output signals not used by the Btu meter.

Both incoming and outgoing connections

are made to the same terminal.

(D) Isolated Analog Common - (Yellow)

Connections shown with (C)

are used with F-1x10 models, including

bi-directional.

Connections shown with (D)

are used with F-1x11 models, including

bi-directional.

Connections shown with (E)

are used with F-1x30 models, including

bi-directional.

Not Used

L1 N

CAUTION

Shield connections are required for proper operation. Failure to use shielded cable or to properly

terminate shield connections may result in erratic operation. Shields should be terminated in

the D-100 at the terminals provided. The shield connection at the flow meter should be left

unterminated.

!

3.3.1.1 ONICON Turbine Flow Meters

ONICON turbine flow meters are provided with a number of different output

configurations. These affect the number of wires contained in the cable attached

to the flow meter. Refer to the diagram below and the laminated tag attached to

the flow meter for specific details.

• Top and bottom turbine signals are only used with the F-1200 and FB-1200

flow

meters.

• Directional contacts are only used by FB-1200 flow meters.

• Terminal block positions are provided for additional flow meter signals that