Caution, F-2000 flow meter connections, Flow meter inputs – ONICON D-100 Flow User Manual

Page 14: Auxiliary flow meter signals

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]

D-100 Flow Display Manual 10/14 - 0634-14 / 18340

Page 14

* 4-20mA -

* 4-20mA +

F-2000 Flow Meter

Connections

(A) Scaled +

(A) Scaled -

Flow Meter Inputs

* Shield

Auxiliary Flow Meter Signals

* Earth

Outputs

Terminal #

* + 24V

* - ILoop

+ 24V

- Pout

* Earth

Connections shown with * are required for all installations. Connections shown with (A) are optional.

1

2

3

4

L1 N

Not Used

CAUTION

Shield and earth connections are required for proper operation. Failure to use shielded cable

or to connect earth to both the flow meter and D-100 may result in erratic operation. Shields

should be terminated at the D-100 shield terminals and left unterminated at the flow meter.

!

3.3.1.4 ONICON F-2500 Flow Meters

F-2500 Flow Meter

Connections