Caution – ONICON D-100 Flow User Manual

Page 13

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]

D-100 Flow Display Manual 10/14 - 0634-14 / 18340

Page 13

Analog Common -

* Frequency -

* Frequency +

F-3100 & F-3200 Flow

Meter Connections

Connections shown with * are required for

all installations.

Connections shown with (A) are required

for bi-directional flow installations.

Connections shown with (B) are optional

for non bi-directional installations.

4-20mA +

(B) Scaled +

(B) Scaled -

Flow Meter Inputs

* Shield

Auxiliary Flow Meter Signals

* Earth

(A) Direction +

(A) Direction -

Outputs

Terminal #

* (+) Pulse Output # 1

* (-) Pulse Output # 1

16

17

(+) Pulse Output # 2

(-) Pulse Output # 2

18

19

(+) 4-20mA Output

(-) 4-20mA Output

9

10

(+) Pulse Output # 2

(-) Pulse Output # 2

18

19

Note: The D-100 does not provide power to the F-3100 or F-3200 flow

meter. Input power for the flow meter must be provided separately. See

flow meter manual for detailed wiring instructions.

* Earth

L1 N

Not Used

CAUTION

Shield and earth connections are required for proper operation. Failure to use shielded cable

or to connect earth to both the flow meter and D-100 may result in erratic operation. Shields

should be terminated at the D-100 shield terminals and left unterminated at the flow meter.

!

CAUTION

The D-100 internal 24 V power supply cannot provide power to the F-3100 or F-3200 flow meters.

!

3.3.1.3 ONICON F-3100 and F-3200 Flow Meters