Flow meter inputs, Auxiliary flow meter signals, Caution – ONICON D-100 Flow User Manual

Page 12: Shield, Earth (green/yellow), G60hz, Led1 t1, Var1

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]

D-100 Flow Display Manual 10/14 - 0634-14 / 18340

Page 12

3.3.1.2

Input Signal Connections from F-3500 Flow Meter

3.3.1.3

Input Signal Connections from FB-3500 Flow Meter

J1

5

G

60HZ

1

J2-1

+1

5

+24

J2-12

G

G

10

R7

H3

R1

20075-50 REV. A

LED1

T1

D1

D2

VAR1

F1

1/8 AMP

TB1

D4

D3

H1

1

Connections shown for T5-1 and T5-2

are for the same analog output from the

FB-3500. This output can be configured in

the flow meter as a 4-20mA or 0 -10 VDC.

0-10 VDC + (Blue)

* Frequency - (Yellow)

* 24VDC Supply + (Red)
* Supply Common - (Black)

* Frequency + (Green)

FB-3500 Flow Meter Connections

Connections shown with * are required.

4-20mA + (Blue)

Flow Meter Inputs

* Shield

Auxiliary Flow Meter Signals

Isolated Analog Common - (Brown)

Earth (Green/Yellow)*

Factory Installed Cable

T4

1

2

3

4

5

6

7
8

9

10

11

12

13

* Direction - (White / Black)

* Direction + (Orange / Black)

T5

1

2

3

4

5

6

Alarm - (White)

Alarm + (Orange)

Connections shown below dashed line

are for flow meter output signals not used

by the BTU meter. Both incoming and

outgoing connections are made to the

same terminal.

L1 N

Not Used

!

CAUTION

See FB-3500 installation and operation guide for additional information on properly grounding the meter.

J1

5

G

60HZ

1

J2-1

+1

5

+24

J2-12

G

G

10

R7

H3

R1

20075-50 REV. A

LED1

T1

D1

D2

VAR1

F1

1/8 AMP

TB1

D4

D3

H1

1

Connections shown for T5-1 and T5-2

are for the same analog output from the

F-3500. This output can be configured in

the flow meter as a 4-20mA or 0 -10 VDC.

0-10 VDC + (Blue)

* Frequency - (Yellow)

* 24VDC Supply + (Red)
* Supply Common - (Black)

* Frequency + (Green)

F-3500 Flow Meter Connections

Connections shown with * are required.

4-20mA + (Blue)

Flow Meter Inputs

* Shield

Auxiliary Flow Meter Signals

Isolated Analog Common - (Brown)

Earth (Green/Yellow)*

Factory Installed Cable

T4

1

2

3

4

5

6

7
8

9

10

11

12

13

T5

1

2

3

4

5

6

Alarm - (White)

Alarm + (Orange)

Connections shown below dashed line

are for flow meter output signals not used

by the BTU meter. Both incoming and

outgoing connections are made to the

same terminal.

L1 N

Not Used

!

CAUTION

See F-3500 installation and operation guide for additional information on properly grounding the meter.

Connections shown below dashed line

are for flow meter output signals not

used by the D-100. Both incoming and

outgoing connections are made to the

same terminal.

Connections shown below dashed line are

for flow meter output signals not used by

the D-100. Both incoming and outgoing

connections are made to the same

terminal.