3.3.2 Frequency / Pulse Flow Input (Di2)

The D-100 is provided with a separate input for frequency or scaled pulse flow signals,

(T4, terminals 6 and 7). This input can be configured to accept an active, positive going

pulse (5-24 VDC) output signal, an open collector output signal or a contact closure (dry

contact) output. The maximum input frequency is 500 Hz. Contact ONICON for technical

assistance in configuring and programming this input. When this flow input is used the

display menu pages will indicate Di2 on the rate and total(s) pages.

T3

1
2
3
4
5

T4

1
2
3
4
5
6
7
8
9

10
11
12
13

T5

1
2
3
4
5
6

ANALOG INPUTS

SIGNAL
REFERENCE
SIGNAL
REFERENCE
SHIELDS

24 VCD SUPPLY +
SUPPLY COMMON -
SHIELD
4-20 mA +
4-20 mA -
FREQUENCY +
FREQUENCY -
DIRECTION +
DIRECTION -
ALARM +
ALARM -
TOP TURBINE
BOTTOM TURBINE

4-20 mA +
0-10 VDC +
ANALOG COMMON -
ISOLATED ANALOG COMMON -
SCALED +
SCALED -

FLOW METER INPUTS

AUXILIARY FLOW METER SIGNALS

Ai4

Ai3

Ai2

Di2

3.3.3 Analog Flow Input (Ai2)

The D-100 is provided with a separate input for analog

flow signals (T4 terminals 4 and 5). This input can be

configured to accept active or passive (loop powered)

4-20 mA signals. Contact ONICON for technical

assistance in configuring and programming this input.

When this flow input is used the display menu pages will

indicate Ai2 on the rate and total(s) pages.

3.3.4 Directional Contacts

The D-100 is provided with a separate input for

determining flow direction. Connections for this input

are made at T4 terminals 8 (+) and 9 (-). This input can be

connected to a non- polarized contact closure relay or an

open connector output. Note that the input is polarized

for sinking (NPN) open collector outputs. Totals will

accumulate in the (+) Mode 1 registers whenever the

contacts are closed.

3.3.5 Ai3 and Ai4 Analog Inputs

The D-100 can be provided with two optional analog

inputs capable of powering any standard 4-20mA loop

powered sensor. The inputs can also be configured

from the factory to accept an active (powered) 4-20mA

signal. Rate data from the two sensors is available via the

network interface and the analog 4-20mA signals can be

replicated via the optional multi-analog output board.

Analog input Ai3 is connected to T3 terminals 1 (+) and

2 (-). Analog input Ai4 is connected to T3 terminals 3 (+)

and 4 (-). Do not exceed 4.5 in-lb (0.5 Nm) of torque,

when tightening the terminals.

3.3.6 Digital Pulse Input (Di3)

The D-100 can be provided with an optional digital pulse input. This option is only

available on displays provided with serial communications. It allows the D-100 to receive

a pulse input from an external device such as a power meter or gas meter. The pulses are

totalized in an internal register and are available via the serial communications network.

This register can be zeroed on demand via the front panel or over the network. When this

pulse input is used the display menu page will indicate Di3 on the total page. Contact

ONICON for more information.