3.3.7 Totalizer Outputs and Mode Status

For unidirectional flow applications, the output relay for

flow total is located on the mother board at T1, terminals 1

and (+) 2 mode 1. The value of each “closure” is listed on

the configuration data sheet and is the same as the flow total

multiplier displayed on the LCD (example: each closure = 100

Gallons). This information is also included on a label inside

the D-100. For bi-directional flow applications, connections

for the (+) mode 1 flow total output relay are at T1 terminals 1

and 2. The (-) mode 2 flow total output relay connections are at

T1 terminals 3 and 4. Flow direction is indicated by the mode

status output (T1 pins 5 and 6). The table below describes the

relationship between (+) mode 1 and (-) mode 2 totals and

forward and reverse flow for ONICON insertion turbine and

inline electromagnetic flow meters. Do not exceed 4.5 in-lb (0.5

Nm) of torque, when tightening the terminals.

OUTPUTS

TOTALIZER OUTPUT

MODE 1

TOTALIZER OUTPUT

MODE 2

MODE STATUS

CHANNEL A

ANALOG OUTPUT

CHANNEL B

ANALOG OUTPUT

CHANNEL C

ANALOG OUTPUT

CHANNEL D

ANALOG OUTPUT

ALARM

OUTPUT

+
_

+
_

+
_
+
_

T1

1
2
3
4
5
6
7
8
9

10
11
12
13
14
15
16
17
18

Flow Meter

Model

Flow Direction

Relative to Direction

Arrow on Meter

Flow Meter

Output Condition

D-100 Mode

Status Indicator

(T1 - Pins 5 & 6)

D-100 Register

Accumulating

Totals

FB-1200 Series

Flow in the direction
of arrow

Closed contact

Open contact

+ Mode 1

FB-1200 Series

Flow reverse from
direction arrow

Open contact

Closed contact

- Mode 2

F-3000 Series

Flow toward (+) sign

Not energized

(open)

Closed contact

- Mode 2

F-3000 Series

Flow toward (-) sign

Energized

(closed)

Open contact

+ Mode 1

F-4000 Series

Flow forward (-) sign

Energized

(closed)

Open contact

+ Mode 1

F-4000 Series

Flow forward (-) sign

Not Energized

(open)

Closed contact

- Mode 2

3.3.8 Isolated Analog Outputs

The D-100 can be configured to provide up to four isolated analog outputs. These

outputs can be used to replicate the incoming analog signals. The output signal type

can be 4-20 mA, 0-10 VDC or 0-5 VDC and is field configurable. Contact ONICON for

assistance in reconfiguring or reprogramming the analog inputs. See the configuration

data sheet provided or the label located inside the D-100 for output specific configuration

information. Analog output signal connections are made at T1 terminals 7 through 14.

Do not exceed 4.5 in-lb (0.5 Nm) of torque, when tightening the terminals.

(+)

(-)