SECTION 4.0: D-100 START-UP AND COMMISSIONING

4.1 DISPLAY AND KEYPAD

The display contains two lines of alphanumeric characters. The first line displays the numerical

value of the quantity described by the second line of the display. The second line contains the

engineering units and a multiplier, which can range from 1 to 1,000,000. The multiplier is the

value which the number on the top line must be multiplied by to achieve the correct value.

Three membrane keys are provided to operate the display

and program the meter.

When operating in the RUN mode, the SCROLL button

advances the display from one page to the next. A total of

up to eight different pages may be available for display

depending on whether the flow meter is unidirectional or

bi-directional.

The RESET button, if enabled, allows totals to be reset to zero.

The PROGRAM button is not active when operating in the

RUN mode.

4.2 PROCESSOR START-UP

When power is applied to the display, alphanumeric characters appear on the two lines of the

display indicating the display is operating. Press and release the SCROLL button on the front

panel. Observe the display cycle to the next page.

Successively pressing the SCROLL button will cycle the display through the run mode pages

summarized in the tables below.

Select the FLOW RATE page. Note the displayed flow rate. Confirm that the flow rate value is in

the correct range.

Unidirectional Flow

Page No.

Display Name

Selectable Units

1

Flow Total Ai2/Di2

Gal, Liter, M

3

, lb mass, kg mass, Ft

3

, SCF, NCM

2

Flow Rate Ai2/Di2

GPM, GPH, MGD, l/s, l/min, l/hr, M

3

/hr, Ft

3

/m, lb/hr, kg/hr,

SCFH, SCFM, NCMH

3

Analog Input Ai3

DEG F, DEG C, PSI, BAR, KPASCL, GPM, L/S, M3/H, CFS, CFM,
KBTU/H, KW, TON, %RH, SCFM, SCFH, NCMH, None

4

Analog Input Ai4

DEG F, DEG C, PSI, BAR, KPASCL, GPM, L/S, M3/H, CFS, CFM,
KBTU/H, KW, TON, %RH, SCFM, SCFH, NCMH, None

5

Digital Input Di3

PULSE COUNT ONLY (Engineering units entered as text)

6

Alarm Status

None

7

Serial Number

None

GAL X 100