Three phase ups systems 1. system overview – OnLine Power Battery Backup System User Manual

Page 26

Advertising
background image

OLP

Three Phase UPS Systems

1. SYSTEM OVERVIEW

1-22

HIGH DC – the LED will light as long as the DC voltage is over 430VDC.

BAT LOW – the LED will light as long as the DC voltage is lower than

320VDC.

BAT LOW STOP – the LED will light as long as the DC voltage is lower than

295VDC, inverter cannot start.

FAULT – the inverter is shutdown due to abnormal conditions such as

overload, short circuit, high DC, fuse over temperature, bypass breaker on
or emergency stop.

Since these LEDs are located behind the transparent window, the user can see
them clearly without opening the door.

D: Audible (buzzer) alarm: The user should not be expected to watch the UPS all

the time. Therefore, when abnormal conditions occur, an audible sound should
be emitted to warn the user to check the status of the UPS. The alarm buzzer will
beep under any one of the following conditions:

INVERTER IS OVERLOADED-

>110%, beep once / 3 seconds

>125%, beep once / second

>150%, beep twice / second

BACK- UP

>320VDC, beep once / 3 seconds

<320VDC, beep twice / second

<295VDC, no beeping

INVERTER IS SHORT CIRCUITED - beep continuously

FUSE BROKEN - beep continuously

HEAT SINK OVER TEMPERATURE - beep continuously

HIGH DC SHUTDOWN - beep continuously

BYPASS ON STOP - beep continuously

EMERGENCY STOP – (emergency power off) beep continuously

The buzzer will also beep once every time the inverter is switched on or off to
acknowledge to the user that his key is valid and accepted.