Three phase ups systems 2. technical – OnLine Power Battery Backup System User Manual

Page 31

Advertising
background image

OLP

Three Phase UPS Systems

2. TECHNICAL

3

KVA 80

100

120

160

OVERALL CHARACTERISTICS

OVERALL EFFICIENCY

92.5%

92.5%

93%

93%

OPERATING ENVIRONMENT:

- TEMPERATURE

0 -40℃ ( 32 - 104℉ )

- HUMIDITY

0% - 90% ( NON–CONDENSING )

- ALTITUDE

<1500 M ABOVE SEA LEVEL

TYPICAL HEAT
DISSIPATION (BTU)

5280 6600 7900 10,533

WEIGHT(lbs) (No Battery) 1760

2420

2860

3300

DIMENSION:

- HEIGHT

62”

- WIDTH

43”

- DEPTH

22”

- AUDIBLE NOISE

< 65 dBA (@ 1 m)

STANDARDS:

- EN50091-1,-2

YES

- FCC CLASS A

YES

PROTECTIONS:

- SHORT CIRCUIT

RECTIFIER, RESERVE, BYPASS NFB

- LIGHTNING

MOV

- EMC FILTER

INPUT & OUTPUT

- GALVANIC ISOLATION

BETWEEN INPUT & OUTPUT

DATA DISPLAY BY LCD

YES

INDICATIONS & ALARMS:

- LED,LCD,BUZZER

YES

DRY CONTACT

YES

BATTERY START

YES

☆ All specifications are subject to change without prior notice.