Three phase ups systems 3.0 instalation – OnLine Power Battery Backup System User Manual

Page 37

Advertising
background image

OLP

Three Phase UPS Systems

3.0 INSTALATION

3-6

FUSE RATING & CABLE SIZE FOR BATTERY

THE BATTERY VOLTAGE IS 295 – 410V

KVA Imax(A) FUSE(A)

CABLE

AWG

60 180

200

000

80

240

125*2

2 x 2

100

300

160*2

0 x 2

120 360 200*2 000

x

2

160 480 200*2 000

x

2